Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0073

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 31-Aug-2026 20:53 BD time

Site & Handover Details

Site CodeSYL_X0073ZoneSylhet
HOTO Date2026-08-30DistrictSylhet
Handover OrgDhaliTakeover OrgAlliance Computers Limited
Handover PersonMd.Bulbul AhomedTakeover PersonMd. Ismail hossain
Handover Phone01406394565Takeover Phone01847426858
Inspected Byismail sirajiSecurity GuardYes

Generator Information

DG BrandFg wilsonGenset Asset No.000
Capacity (KVA)22TypeCan
Fuel Tank Capacity70Present RH42.2
Fuel (no water)14 LFuel (total)14 L
Water Amount00 LFuel Amount (word)Fourtin
DG Present StatusNOK Genset ON AlarmOK
Battery BrandHamko 100AhBattery SerialP8199420039
Battery AH100Engine Serial35212u9527765
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date
Key Status β€” BTSLocalKey Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks00
Faulty/Disconnected DG00Faulty/Disconnected Tanks1

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)45
Frequency (Hz)49.2Phase3 Phase
OutputAc voltegVoltage L1-L2398
Voltage L2-L3397Voltage L3-L1398
Voltage L1-N229Voltage L2-N229
Voltage L3-N228Current Line 115
Current Line 215Current Line 315
N-G.345Engine BrandParkings
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation per BL StandardOKFuel Preserved at Safe LocationNOK
Exhaust Fan / Ventilation SufficientOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionNOK
Runs in Auto & Manual ModeOKGENSET ON Alarm FunctioningOK
Lub Oil StatusOKRH Meter Working ProperlyOK
No Parts MissingOK

Snags Found (0)

No snags logged for this visit.

Deficiencies & Safety Remarks

DG Major Deficiencies1.DG Battery faulty 2.DG Battery cable aluminum need to change 3.Hose pipe leakage 4.Hi temperature sensor broken 5.DG Dynamo faulty 6.Silencer pipe leakage 7.DG Room gate Broken. 8.DG Canopy lock faulty 9.1 Phase missing 10.Fuel theft poren area need to poper protection.
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md.Bulbul Ahomed
Handed Over By · Dhali
01406394565
Date:  
Md. Ismail hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Download / Print PDFEdit Before Printing