Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0043

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 31-Aug-2026 19:55 BD time

Site & Handover Details

Site CodeSYL_X0043ZoneSylhet
HOTO Date2026-08-31DistrictSunamganj
Handover OrgDhaliTakeover OrgAlliance Computers Limited
Handover PersonMd. Eidris AliTakeover PersonMd. Ismail hossain
Handover Phone01750537433Takeover Phone01847426858
Inspected Byismail sirajiSecurity GuardNo

Generator Information

DG BrandFg wilsonGenset Asset No.20060052IRD
Capacity (KVA)22TypeCan
Fuel Tank Capacity2000Present RH442.8
Fuel (no water)186 LFuel (total)149 L
Water Amount37 LFuel Amount (word)One hundred fourty nine
DG Present StatusOK Genset ON AlarmOK
Battery BrandHamkoBattery SerialP033WECK0207
Battery AH100Engine SerialHP51109U981641P
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-05-24
Key Status β€” BTSLOCALKey Status β€” DG RoomLOCAL
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DG00Faulty/Disconnected Tanks00

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)24
Frequency (Hz)50Phase3 Phase
Output400Voltage L1-L2402
Voltage L2-L3400Voltage L3-L1401
Voltage L1-N232Voltage L2-N232
Voltage L3-N230Current Line 18
Current Line 28Current Line 38
N-G3.354Engine BrandParkings
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation per BL StandardOKFuel Preserved at Safe LocationOK
Exhaust Fan / Ventilation SufficientOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionOK
Runs in Auto & Manual ModeOKGENSET ON Alarm FunctioningOK
Lub Oil StatusNOKRH Meter Working ProperlyOK
No Parts MissingOK

Snags Found (2)

Snag #CategoryComponentStatusObservationsAction
S-003 DG - Battery/Starter (unspecified) Faulty 1) Dg fan belt loss, 2)charging dynamo poparly not setting 3) engine loop oil shortest Open
S-004 DG - Battery/Starter (unspecified) Faulty 1) Dg fan belt loss, 2)charging dynamo poparly not setting 3) engine loop oil shortest Open

Deficiencies & Safety Remarks

DG Major Deficiencies
Safety Remarks
General Remarks1) Dg fan belt loss, 2)charging dynamo poparly not setting 3) engine loop oil shortest

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md. Eidris Ali
Handed Over By · Dhali
01750537433
Date:  
Md. Ismail hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  